Wood chip boiler
Cascades up to 2 MW
Between 2 and 6 Eco-HK boilers. When one is being serviced, the others keep running.
- output per boiler
- 70–330 kW
- base models
- 14
- fuel
Wood chips

Cascade control
Automatic control of up to 6 boilers
Eco-HK wood chip boilers can be combined in cascade from 70 kW up to 2 MW. The cascade controller switches the boilers on and off as required and distributes the load evenly between them.
Combination of 2 to 6 boilers
Total output up to 2 MW
Centralised cascade control
Extended life through automatic balancing
Minimum starting power of 70 kW
Features and equipment
The points below are taken from the Hargassner documentation.
- Continued operation during servicing
- At low load, only some of the boilers run
- The cascade control is configured for each installation
- Efficient operation with low costs
- The installed output can be extended later
- Eco-HK base boilers from 70 to 330 kW
How a cascade is configured.
The number of boilers, the load distribution and operation during servicing.
- 01
Choose the base model between 70 and 330 kW
- 02
Combine 2 to 6 boilers as needed
- 03
The cascade controller manages start-ups and shutdowns
- 04
The load is automatically distributed between the units
- 05
The configuration can be extended over time
- 06
The system keeps running even while one unit is being serviced
Choose the base boilers.
14 base models from 3 ranges, combinable in cascade. We set the configuration from a heat-load calculation.
Eco-HK 70-120 kWEco-HK 70
70kW
rated output
Adjusts its output between 21 and 70 kW according to the heat demand.
- Efficiency (NCV)
- 95.6*%
- Seasonal efficiency
- 83** / 83**%
- Energy class
- A++
- Dimensions (W × H × D)
- 875 × 1610 × 1560mm
- Weight
- 1100kg
- Floor space
- 1.15m²
Technical data for every model.
Figures from the Hargassner datasheets for the Cascades up to 2 MW range. Pick a column to see that model in detail.
| Eco-HK 70-120 kW | Eco-HK 130-230 kW | Eco-HK 250-330 kW | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Model | ||||||||||||||
| Rated output · kW | 70 | 90 | 99 | 108 | 120 | 130 | 149 | 166 | 199 | 216 | 226 | 249 | 299 | 330 |
| Fuel heat input · kW | 73.2 | 94.4 | 105.5 | 115.4 | 126.6 | 137.3 | 157.3 | 175.7 | 210.8 | 229.1 | 239.9 | 264.6 | 318.8 | 352.6 |
| Minimum output · kW | 21 | 27 | 29.7 | 32.4 | 36 | 39 | 44.7 | 49 | 59 | 59 | 67.8 | 74.7 | 89.7 | 99 |
| Efficiency (NCV) at rated output · % | 95.6* | 95.3* | 95.2* | 95* | 94.8* | 94.7* | 94.7* | 94.5* | 94.4* | 94.3* | 94.2* | 94.1* | 93.8* | 93.6* |
| Efficiency (NCV) at 30 % load · % | 95.2 | 95.6 | 95.8 | 96 | 96.2 | 96.3 | 96.5 | 96.7 | 97 | 96.9 | 96.9 | 96.8 | 96.5 | 96.4 |
| Efficiency (GCV) at rated output · % | 87.5 | 87.3 | 87.2 | 87.1 | 87 | 86.6 | 85.6 | 84.6 | 83.2 | 83.2 | 83.8 | 83.3 | 83.3 | 83.4 |
| Efficiency (GCV) at 30 % load · % | 87.1 | 87.5 | 87.7 | 87.9 | 88.1 | 87.8 | 87.2 | 86.5 | 85.5 | 85.7 | 85.8 | 86 | 86.4 | 86.7 |
| Seasonal space heating efficiency (ηs) · % | 83** / 83** | 84** / 83** | 84** / 83** | 84** / 83** | 84** / 84** | 84** / 84** | 84** / 84** | 83** / 84** | 82** / 85** | 82** / 86** | 82** / 86** | 82** / 82** | 83** / 83** | 83** / 83** |
| Boiler temperature range · °C | 69 - 90 (opt. 95) | 69 - 90 (opt. 95) | 69 - 90 (opt. 95) | 69 - 90 (opt. 95) | 69 - 90 (opt. 95) | 69 - 90 (opt. 95) | 69 - 90 (opt. 95) | 69 - 90 (opt. 95) | 69 - 90 (opt. 95) | 69 - 90 (opt. 95) | 69 - 90 (opt. 95) | 69 - 95 | 69 - 95 | 69 - 95 |
| Dimensions (W × H × D) · mm | 875 × 1610 × 1560 | 875 × 1610 × 1560 | 875 × 1610 × 1560 | 875 × 1610 × 1560 | 875 × 1610 × 1560 | 875 × 1765 × 1790 | 875 × 1765 × 1790 | 875 × 1765 × 1790 | 945 × 1915 × 1905 | 945 × 1915 × 1905 | 945 × 1915 × 1905 | 1155 × 2015 × 2285 | 1155 × 2015 × 2285 | 1155 × 2015 × 2285 |
| Weight · kg | 1100 | 1100 | 1150 | 1150 | 1150 | 1450 | 1450 | 1450 | 1600 | 1600 | 1600 | 2500 | 2500 | 2500 |
| Floor space required · m² | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.37 | 1.37 | 1.37 | 1.80 | 1.80 | 1.80 | 2.62 | 2.62 | 2.62 |
| Flue pipe diameter · mm | 180 | 180 | 180 | 180 | 180 | 200 | 200 | 200 | 250 | 250 | 250 | 250 | 250 | 250 |
| Ash box volume · l | 60 | 60 | 60 | 60 | 60 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 |
| Water content · l | 180 | 180 | 180 | 180 | 180 | 253 | 253 | 253 | 360 | 360 | 360 | 570 | 570 | 570 |
| Flow / return connection · in | 6/4 | 6/4 | 6/4 | 6/4 | 6/4 | 2 | 2 | 2 | 2.5 - 2 | 2.5 - 2 | 2.5 - 2 | 2.5 | 2.5 | 2.5 |
| Energy efficiency class | A++ | not available | not available | not available | not available | not available | not available | not available | not available | not available | not available | not available | not available | not available |
Values marked * refer to the notes in the Hargassner datasheet.
“–” = value not available for that model.
Swipe for all models
Recommended accessories
For fuel feeding, controls, storage and hot water, all compatible with Cascades up to 2 MW.
AccessoriesOekoRonaFine dust filter for boilers from 250 kW.Details
AccessoriesFresh water stationHygienic hot water generator.Details
AccessoriesSubstationsCompact external heat supply.Details
AccessoriesHeat metersReliably measures energy consumption.Details
AccessoriesHeating circuit groupsCompact heating circuit groups.Details
AccessoriesAsh removal systemsFor wood chip and pellet boilers.Details
Fuel extraction systemECO fuel extraction systemECO fuel extraction with a low-consumption drive.Details
Heating modulesHeating moduleCombined boiler room and fuel store.Details
Cascades installed by Perfect Energy.
Installations with the same base boilers, connected in cascade and commissioned by the Perfect Energy team.
All wood chip ranges
Request a quote for Cascades up to 2 MW.
Send us the building data: its use, the floor area and the available fuel. An engineer recommends the model; the final quote is issued after the technical assessment.
- Free technical consultation
- Authorised Hargassner dealer
- Delivery and installation in Austria and Germany